Customization: | Available |
---|---|
Breaking Capacity: | Low Voltage Circuit Breakers |
Operation: | Electric Type |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Application
Circuit Breaker Specification:
Frame class Rated current InmA | Conventional Rated heat current Ith A | Rated current A | Short circuit breaking capacity class | Short circuit breaking capacity kA(Effective value) Icu/Ics | |
AC 400V | AC 690V | ||||
63 | 63 | 10,16,20,25,32,40,50,63 | L | 25/18 | / |
M | 50/35 | / | |||
H | 85/50 | / | |||
125(100) | 125(100) | 16,20,25,32,40,50,63,80,100,125 | C | 25/18 | 10/5 |
L | 35/22 | 10/5 | |||
M | 50/35 | 20/10 | |||
H | 80/50 | 20/10 | |||
250(225) | 250(225) | 100,125,140,160,180,200,225,250 | C | 25/18 | 10/5 |
L | 35/22 | 10/5 | |||
M | 50/35 | 20/10 | |||
H | 80/50 | 20/10 | |||
400 | 400 | 225,250,315,350,400 | L | 50/35 | 10/5 |
M | 65/42 | 20/10 | |||
H | 100/65 | 20/10 | |||
630 | 630 | 400,500,630 | L | 50/35 | 10/5 |
M | 65/42 | 20/10 | |||
H | 100/65 | 20/10 | |||
800 | 800 | 630,700,800 | M | 65/50 | 30/15 |
H | 100/65 |
Circuit Breaker Tripping Characteristics:
Rated current of release (A) | Thermodynamic release(ambient temp+40) | Operational current of magneticrelease (A) | |||
1.05In(cold state) inoperative time (h)
|
1.I3n 0h(eat state)inoperative time(h) | ||||
In<63 | ≥1 | <1 | 10In±20% | ||
63<In<100 | ≥2 | <2 | 10In±20% | ||
100<In<630 | ≥2 | <2 | 5-10In±20% | ||
Rated current of release (A) | Thermodynamic release(ambient temp+40ºC) | ||||
1.0In (cold state) |
1.20In (heat state) |
1.50In (heat state) |
7.2In (heat state) |
Operational current of magnetic release (A) |
|
12.5<In<400 | ≥2h | <2h | <4min | 2S<Tp<10s | 12In±20% |