Electricity Type: | Vacuum |
---|---|
Number of Pole: | 3 Pole |
Phase: | 3 Phase |
Product Information:
1 Overview
JCZ5-7.2 series indoor AC high voltage vacuum contactor (referred to as a contactor for short) is divided into two types: closing mechanical holding and electromagnetic holding. The contactor is suitable for three-phase AC 50HZ. The rated voltage is 7.2KV. The rated current is up to In the power system of 630A, it is used for long-distance connection and disconnection of lines, control of high-voltage motors, transformers and capacitive loads and other electrical equipment, especially suitable for various frequent operation fields.
The contactor is small in size and light in weight. It adopts the popular international assembly structure of upper and lower arrangement, which is easy to use and maintain, and it is easy to form a complete set of FC circuit equipment.
2. Normal use conditions
a) Upper limit of ambient air temperature; +40 o C, lower limit; -25 o C,
b) The altitude does not exceed 2000M
c) Humidity; the daily average of relative humidity is not more than 95% and the monthly average is not more than 90%; the daily average of water vapor pressure is not more than 2.2KPA, and the monthly average is not more than 1.8KPA.
d) The surrounding air should not be significantly polluted by corrosive or flammable gas and water vapor.
e) No frequent strenuous exercise.
f) When the contactor moves, the inclination angle between the installation plane and the horizontal is not more than 5o .
g) Requirements beyond the above conditions shall be agreed by the user and the manufacturer.
3. Main technical parameters
3.1 Rated parameters
serial number | name | unit | data | |||
JCZ5-7.2J/D-630/400/250 | ||||||
1 | Rated voltage | kV | 7.2 | |||
2 | Rated current | A | 630 | 400 | 250 | |
3 | Rated making current (RMS) | A | 6300 | 4000 | 2500 | |
4 | Rated maximum breaking current | 5040 | 3200 | 2500 | ||
5 | 4S thermal stable current | 6300 | 4000 | 2500 | ||
6 | Limit breaking current | 6300 | 4000 | 2500 | ||
7 | Power frequency withstand voltage | kV | 32 | |||
8 | allowable operating frequency | times/h | 300 | |||
9 | Electrical life | AC-3 | ×10 4 times | 25 | ||
AC-4 | 10 | |||||
10 | Mechanical life | 30 | ||||
11 | Rated operating voltage | IN | AC110 / 220 | |||
12 | Closing coil pull-in current | A | ≤ DC6/3 | |||
13 | hold coil hold current | D:DC0.32/0.16 | ||||
14 | Shunt coil trip current | J : DC2.5 / 1.3 |
serial number | name | unit | data |
JCZ5-7.2J/D-630/400/250 | |||
1 | Contact Spacing | mm | 4.5+1.0/-0.5 |
2 | Contact overtravel | 1.5±0.5 | |
3 | Average closing speed | m/s | 0.1~0.25 |
4 | Average opening speed | 0.3~0.6 | |
5 | Three-phase closing and opening synchronization | ms | ≤ 2 |
6 | Closing time/opening time | ≤ 150/ ≤ 150 | |
7 | Conductive loop resistance of each phase (20 o C) | Ω | ≤ 250 |
Exhibitions:
1.Could I put my own logo on it?
> Sure, customers' logo can be made by laser, engraved, embossed, transfer printing etc.
2.Should I pay extra for logo printing ?
> Normally usd 0.017/per color,according to the actual situation.
3.How about the quality ?
> Acquire the CE & SGS Certification.
> 100% QC in produce process and before package.
4.Could I buy 1pc sample first and small order ?
> Of course, support sample order and small order, especially for new customers under certain condition
5.How much for 1pc sample ?
>Some cheap ones may free for 1pcs but need to see the actual stock.
6.If I have my thoughts, do you have person to design according to my concept?
> Certainly,our design team is willing to do for you.
7.How long to make a sample?
> 2-5 days which depends on the samples' complexity.
8.Is the sample fee refundable or not?
> Sure, refundable once order confirmed.
With more than 15 years OEM experience, we can provide professional solutions for customers.
Send your Inquiry Details in the Below, Click "Send" Now!!!